MAINTENANCE OF SF6 GAS CIRCUIT BREAKERS



PROPERTIES OF SF6 (SULFUR HEXAFLUORIDE) GAS. ­

Toxicity.- SF6 is odorless, colorless,tasteless, and nontoxic in its pure state. It can, however, exclude oxy­gen and cause suffocation. If the normal oxygen content of air is reduced from 21 percent to less than 13 percent, suffocation can occur without warning. Therefore, circuit breaker tanks should be purged out after opening.

Toxicity of arc products.- Toxic decomposition products are formed when SF6 gas is subjected to an electric arc. The decomposition products are metal fluorides and form a white or tan powder. Toxic gases are also formed which have the characteristic odor of rotten eggs. Do not breathe the vapors remaining in a circuit breaker where arcing or corona discharges have occurred in the gas.Evacuate the faulted SF6 gas from the circuit breaker and flush with fresh air before working on the circuit breaker.

Physical properties.- SF6 is one of the heaviest known gases with a density about five times the density of air under similar conditions. SF6 shows little change in vapor pressure over a wide temperature range and is a soft gas in that it is more compressible dynamically than air. The heat transfer coefficient of SF6 is greater than air and its cooling characteristics by convection are about 1.6 times air.

Dielectric strength.- SF6 has a dielectric strength about three times that of air at one atmosphere pressure for a given electrode spacing. The dielectric strength increases with increasing pressure;and at three atmospheres, the dielectric strength is roughly equivalent to transformer oil. The heaters for SF6 in circuit breakers are required to keep the gas fromliquefying because, as the gas liquifies, the pressure drops, lowering the dielectric strength. The exact dielectric strength, as compared to air, varies with electrical configuration, electrode spacing, and electrode configuration.

Arc quenching.- SF6 is approximately 100 times more effective than air in quenching spurious arcing. SF6 also has a high thermal heat capacity that can absorb the energy of the arc without much of a temperature rise.

Electrical arc breakdown.- Because of the arc-quenching ability of SF6,corona and arcing in SF6 does not occur until way past the voltage level of onset of corona and arcing in air.SF6 will slowly ecompose when exposed to continuous corona.

All SF6 breakdown or arc products are toxic. Normal circuit breaker operation produces small quantities of arc products during current interruption which normally recombine to SF6. Arc products which do not recombine, or which combine with any oxygen or moisture present, are normally removed by the molecular sieve filter material within the circuit breaker.

HANDLING NONFAULTED SF6.

The procedures for handling nonfaulted SF6 are well covered in manufacturers' instruction books. These procedures normally consist of removing the SF6 fromthe circuit breaker, filtering and storing it in a gas cart as a liquid, and transferring it back to the circuit breaker after the circuit breaker maintenance has been performed. No special dress or precautions are required when handling nonfaulted SF6.

HANDLING FAULTED SF6.-

Toxicity.-

Faulted SF6 gas.- Faulted SF6 gas smells like rotten eggs and can cause nausea and minor irritation of the eyes and upper respiratory tract. Normally, faulted SF6 gas is so foul smelling no one can stand exposure long enough at a concentration high enough to cause permanent damage.

Solid arc products.- Solid arc products are toxic and are a white or off-white, ashlike powder. Contact with the skin may cause an irritation or possible painful fluoride burn. If solid arc products come in contact with the skin,wash immediately with a large amount of water. If water is not available, vacuum off arc products with a vacuum cleaner.

Clothing and safety equipment requirements.- When handling and removing solid arc products from faulted SF6, the following clothing and safety equipment should be worn:

Coveralls.- Coveralls must be worn when removing solid arc products. Coveralls are not required after all solid arc products are cleaned up.Disposable coveralls are recommended for use when removing solid arc products; however, regular coveralls can be worn if disposable ones are not available, provided they are washed at the end of each day.

Hoods.-Hoods must be worn when removing solid arc products from inside a faulted dead-tank circuit breaker.

Gloves.- Gloves must be worn when solid arc products are hahdied. Inexpensive, disposable gloves are recommended. Nondisposable gloves must be washed in water and allowed to drip-dry after use.

Boots.-Slip-on boots, nondisposable or plastic disposable,must be worn by employees who enter eternally faulted dead-tank circuit breakers. Slip-on boots are not required after the removal of solid arc products and vacuuming. Nondisposable boots must be washed in water and dried after use.

Safety glasses.- Safety glasses are recommended when handling solid arc products if a full face respirator is not worn.

Respirator.- A cartridge, dust type respirator is required when entering an internally faulted dead-tank circuit breaker. The respirator will remove solid arc products from air breathed, but it does not supply oxygen so it must only be used when there is sufficient oxygen to support life.

The filter and cartridge should be changed when an odor is sensed through the respirator. The use of respirators is optional for work on circuit breakers whose interrupter units are not large enough for a man to enter and the units are well ventilated.

Air-line-type respirators should be used when the cartridge type is ineffective due to providing too short a work time before the cartridge becomes contaminated and an odor is sensed.

When an air-line respirator is used, a minimum of two working respirators must be available on the job before any employee is allowed to enter the circuit breaker tank.

Disposal of waste.-All materials used in the cleanup operation for large quantities of SF6 arc products shall be placed in a 55gal drum and disposed of as hazardous waste.

The following items should be disposed of:

a.All solid arc products
b.All disposable protective clothing
c.All cleaning rags
d.Filters from respirators
e.Molecular sieve from breaker and gas cart
f.Vacuum filter element.
http://news.chivindo.com/507/maintenance-of-sf6-gas-circuit-breakers.html

Comments

Popular posts from this blog

Basic PLC Ladder Programming Examples 23

Basic PLC Ladder Programming Examples 23 Basic PLC Ladder Programming Training Examples for Beginners.    Hi friends, here we are starting unique a series of Free Training on PLC Ladder Programming & tutorials. These PLC Ladder Programs are important to learn basics of Ladder programs. Example 7: Sequential control If we serially connect the normally closed contact of Y2 in example 5 to the circuit of Y1 as an AND condition for Y1 (as the diagram in the left hand side), the circuit can not only make Y1 as the condition for Y2, but also allow the stop of Y1 after Y2 is enabled. Therefore, we can make Y1 and Y2 execute exactly the sequential control Example 8: Oscillating circuit The ladder diagram above is a very simple one. When the program starts to scan the normally closed contact Y1, Y1 will be closed because coil Y1 is Off. When the program then scan to coil Y1 and make it On, the output will be 1. When the program scans to the normally closed contact Y1 again in the n...

Merakit pemancar mini FM

Merakit Pemancar mini FM Pemancar fm ini bekerja pada frekuensi 88- 108 MHz  dan memiliki jangkauan radius lebih dari 1 kilometer, tegangan yang digunakan sekitar  9 volt s/d 12 volt DC Pemancar ini menggunakan pcb produk ronica yang banyak dijual di toko elektronik dengan type Ronica SC-197                                                                                                                 Rangkaian ini sangat cocok untuk para pemula yang hobi elektronik. Karena rangkaiannya             sederhana dan komponennya mudah didapatkan di toko toko elektronik. Pemancar fm bisa dijadikan sebagai alat komunikasi geratis, memutar musik, untuk broadsact atau layak nya...

Takbiran Idul Adha 1440 H Jamaah Muda Masjid At Takrim Gapuk

Malam takbiran Idul Adha 1440 H ini terasa kurang afdol kalau tidak diadakan langsung acara takbiran bareng di masjid dan bentuk takbirannya pun bukan dari MP3 maupun CD yang diputar di CD Player lantas ditinggal pergi oleh Marbot masjid. Di Masjid At Takrim Gapuk Dasan Agung Mataram,  para jamaah muda yang tidak ikut pawai takbiran keliling akan berkumpul membentuk halaqoh/kumpulan sambil mengumandangkan bacaan takbiran saling sahut menyahut dengan membentuk pola suara yang uenak di dengar. Dan bila semakin malam maka akan semakin bertambah para jamaah yang ikut serta membaca takbiran hingga larut malam jam 03.00 pagi.  Kalau masalah bergadang hingga larut malam ini,  para jamaah muda ini sudah terbiasa karena mereka setiap malamnya selalu mertadarusan membaca Al Qur'an hingga jam 12.00 WITA. Alloohu akbar Alloohu Akbar Laaailaaha illallohu Alloohu Akbar Alloohu Akbar walillaahilham Gapuk Dasan Agung, malam ahad, 10082019  23.00 WITA  by: AlFuad Gapuki http://n...